IEC 61439-5:2023 低压开关设备和控制设备组件.第5部分:公共网络配电组件
标准编号:IEC 61439-5:2023
中文名称:低压开关设备和控制设备组件.第5部分:公共网络配电组件
英文名称:Low-voltage switchgear and controlgear assemblies - Part 5: Assemblies for power distribution in public networks
发布日期:2023-05-04
标准范围
IEC 61439-5:20 23作为IEC 61439-5:20 23 RLV提供,其中包含国际标准及其红线版本,显示了与上一版本相比技术内容的所有变化。IEC 61439-5:20 23定义了公共电力网络配电组件(PENDA)的具体要求。PENDAs具有以下标准:-用于额定电压不超过1 000 V AC的三相系统(典型配电网见图101)和不超过1 500 V DC的DC系统中的电能分配;-静止的;-本文件不包括开放式组件;-适合安装在只有技术人员才能进入使用的地方,但室外型可以安装在普通人可以进入的地方-拟用于公共电网的能源分配;-室内使用:安装在变电站内部的组件;-户外使用:包含适合露天安装的外壳的组件。这第三版取消并取代了2014年出版的第二版。本版构成技术修订版。与上一版相比,此版本包括以下重大技术变更:a)当外壳由金属材料制成时,省略了在-25°C下进行机械测试的要求;b)增加发电供应和电动汽车充电应用的假设负载系数;c)当PENDA用于具有单独的高压和低压接地的配电变电站时,进行额外的介电测试;d)进一步澄清用于设计验证的代表性样品。
IEC 61439-5:2023 is available as IEC 61439-5:2023 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 61439-5:2023 defines the specific requirements for public electricity network distribution assemblies (PENDAs). PENDAs have the following criteria:
- used for the distribution of electrical energy in three phase systems for which the rated voltage does not exceed 1 000 V AC (see Figure 101 for a typical distribution network) and DC systems not exceeding 1 500 V DC;
- stationary;
- open type assemblies are not covered by this document;
- suitable for installation in places where only skilled persons have access for their use, however, outdoor types can be installed in situations that are accessible to ordinary persons
- intended for use in energy distribution in public power grids;
- indoor use: assemblies for installation inside of electric power substations;
- outdoor use: assemblies containing an enclosure suitable for open air installation.
This third edition cancels and replaces the second edition published in 2014. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) omission of the requirement to conduct mechanical tests at -25 °C when enclosures are made of a metallic material;
b) addition of assumed loading factors generation supplies and electric vehicle charging applications;
c) additional dielectric tests when a PENDA is used in a distribution substation with separate HV and LV earths;
d) further clarification of representative samples for design verification.